Resistive&Inductive(RL) Load Bank
OREN-Resistive&Inductive(RL) Load Bank is mainly used for Generator testing at power station, AC power supply, data center and other testing,May detect the performance of different loads of the AC power supply of the power station.The power input is uniformly optimized to meet the needs of different loads.
Resistive&Inductive(RL) Load Bank
OREN-Resistive&Inductive(RL) Load Bank is mainly used for Generator testing at power station, AC power supply, data center and other testing,May detect the performance of different loads of the AC power supply of the power station.The power input is uniformly optimized to meet the needs of different loads.
Technical Specifications
Models
AC230V-10kW-RL
AC480V-30kW-RL
AC480V-60kW-RL
AC480V- 100kW-RL
AC480V-200kW-RL
AC480V-500kW-RL
Capacity
Resistive load:
10kW
Inductive load:
25kVAR
Resistive load:
30kW
Inductive load:
22.5kVAR
Resistive load:
60kW
Inductive load:
45kVAR
Resistive load:
100kW
Inductive load:
75kVAR
Resistive load:
200kW
Inductive load:
150kVAR
Resistive load:
500kW
Inductive load:
375kVA
Rated
Voltage
Single
Phase,
AC230V
Three Phase
AC480V,
or units can
be specified by customer
Customized
solutions could be available upon request.
Rated current at 480VAC
Resistive
amperes
per phase:
26A
Reactive
amperes
per phase:
20A
Resistive
amperes
per phase:
36A
Reactive
amperes
per phase:
27A
Resistive
amperes
per phase:
72A
Reactive
amperes
per phase:
54A
Resistive
amperes
per phase:
120A
Reactive
amperes
per phase:
90A
Resistive
amperes
per phase:
240A
Reactive
amperes
per phase:
180A
Resistive
amperes
per phase:
601A
Reactive
amperes
per phase:
451A
PF
PF=0.8(or
customized power factor)
Minimum
Load Step
100W ,
100VAR
100W ,
100VAR
100W ,
100VAR
1kW , 1kVAR
1kW , 1kVAR
1kW , 1kVAR
Display
Voltage,
Current, Frequency, Power and PF displayed by digital meter
Protection
Overheating
alarm, Short circuit protection, Overheating protection, Fan overloading
protection, Emergency stop button. All protections can be configured
optionally
Control
Mode
Manual
control by MCBs or push buttons
Air Flow
Horizontal, Force-air
cooling
Dimension
48*60*27(cm)
90*90*160(cm)
90*90*200(cm)
120*120*200(cm)
90*90*200(cm)
120*120*200(cm)