OREN-DC2V-96V Battery Load Bank

Battery Discharger Tester focus on work for the capacity test of NiCD and Lead-acid storage battery as back-up power supply and store solar energy ,wind energy hydroenergy and so on . Cell battery voltage : 1.2V/2V/6V/12V Battery string voltage : 24V/48V/72V/80V/96V/110V/220V /380V/600V

Send enquiry
Product details

OREN-DC2V-96V Battery Load Bank

   Battery Discharger Tester focus on work for the capacity test of NiCD and Lead-acid storage battery as back-up power supply and store solar energy ,wind energy hydroenergy and so on .

Cell battery voltage : 1.2V/2V/6V/12V 

Battery string voltage :  24V/48V/72V/80V/96V/110V/220V /380V/600V

Which  adopts advanced testing technology theory, has obtained a series of breakthrough in research and application of new technology, new parts, new material and new techniques, which is designed in accordance with the requests of international  related testing and maintenance regulations and it is a special detection instrument for the performance detection of stationary battery

 Main Functions

1. do capacity evaluation for battery string

2. do online monitoring for each cell , know voltage , current and capacity

3. do constant current and constant power discharge work

Main Features

1. 7 inch touch screen display , also can use touch pen to operate

2. low voltage & over voltage protection; overload protection; reverse polarity protection

3. check testing data from the equipment or save into SD card and copy to PC

4. install professional analysis software in PC and generate testing report in word and excel format

Application Area

1. Telecommunication carrier base station

2. IT Enterprise and Data centers

3. Golf cart, forklift and truck battery

4. Solar Power System battery

5. Oil, Gas , Mining , power plant

6. UPS System 

Product Appearance Display  

                           

Parameters setup

Turn on the instrument the screen will display “Specs settings”, “Specs template”, “Data management”, “System settings”

 

                                A.jpg

 Online monitor specs settings

Main interface from ”Test Setup ” ---- " Monitor",  enter into  online monitor settings interface.

 

                             F.jpg

 Interface of setup of discharge parameters

Turn on the tester and enter into the interface below , choose “Test Setup” — “Discharge”, enter into interface of discharge parameter

 

                            C.jpg

 Histogram of cell voltage 

To click the histogram will display the voltage of one battery.

 

                             B.jpg

Check all testing data from softwre in PC 

 Online monitor and discharge test could view test data, test pattern, cell contrast, maintenance solution.

                          E.jpg

Technical Index

Model

                                      2V-96V

String Voltage measurement range

12120V

Constant discharge voltage range

10V-60V

60V-120V

Discharge current Range

12V: 60A; 24V: 120A; 

36V: 180A;48V: 200A

72V: 170A; 96V: 200A

String Voltage Resolution

0.01V

Voltage measurement accuracy

≤±0.5%

Cell Voltage Resolution

0.01V

Discharge Voltage of Constance current and constant power

1-200A

Current Measurement Resolutions

0.1A

Cell voltage measurement type

1.2V/2V: 0-4V; 6V:0-8V; 12V: 0-15V

Power Supply

220VAC±15%   50Hz/60Hz

Cooling mode

Air Cooling

Communication Mode

USB Communication port and SD Card storage

Display

7inch Touch screen

High-Voltage insulation test

Input-The enclosure2200Vdc 1min

Input-Output2200Vdc 1min

Output- The enclosure700Vdc 1min

Safety standard

EN610950

Work Temperature

-550

Storage Temperature

-4070

Humidity

Relative humidity 090%40±2

Noise

<60dB

Dimensions of host tester

 

550(L)x360(W)x640mm(H)

Alloy Carrying case

590(L)x520(W)x740mm(H)

Net Weight

                     48Kg