中文简体 English

Telephone: ++86 029-68229739

E-mail: sales@oren-electric.com

Current location: Home > Product > Contents

OREN-DC10-480V-110A Battery Load Bank

Battery Discharger Tester focus on work for the capacity test of NiCD and Lead-acid storage battery as back-up power supply and store solar energy ,wind energy hydroenergy and so on . Cell battery voltage : 1.2V/2V/6V/12V Battery string voltage : 24V/48V/72V/80V/96V/110V/220V /380V/600V

Send enquiry
Product details

OREN-DC10-480V-110A Battery Load Bank

   Battery Discharger Tester focus on work for the capacity test of NiCD and Lead-acid storage battery as back-up power supply and store solar energy ,wind energy hydroenergy and so on .

Cell battery voltage : 1.2V/2V/6V/12V 

Battery string voltage :  24V/48V/72V/80V/96V/110V/220V /380V/600V

Which  adopts advanced testing technology theory, has obtained a series of breakthrough in research and application of new technology, new parts, new material and new techniques, which is designed in accordance with the requests of international  related testing and maintenance regulations and it is a special detection instrument for the performance detection of stationary battery

 Main Functions

1. do capacity evaluation for battery string

2. do online monitoring for each cell , know voltage , current and capacity

3. do constant current and constant power discharge work

Main Features

1. 7 inch touch screen display , also can use touch pen to operate

2. low voltage & over voltage protection; overload protection; reverse polarity protection

3. check testing data from the equipment or save into SD card and copy to PC

4. install professional analysis software in PC and generate testing report in word and excel format

Application Area

1. Telecommunication carrier base station

2. IT Enterprise and Data centers

3. Golf cart, forklift and truck battery

4. Solar Power System battery

5. Oil, Gas , Mining , power plant

6. UPS System 

Product Appearance Display  

                           

Parameters setup

Turn on the instrument the screen will display “Specs settings”, “Specs template”, “Data management”, “System settings”

 

                                A.jpg

 Online monitor specs settings

Main interface from ”Test Setup ” ---- " Monitor",  enter into  online monitor settings interface.

 

                             F.jpg

 Interface of setup of discharge parameters

Turn on the tester and enter into the interface below , choose “Test Setup” — “Discharge”, enter into interface of discharge parameter

 

                            C.jpg

 Histogram of cell voltage 

To click the histogram will display the voltage of one battery.

 

                             B.jpg

Check all testing data from softwre in PC 

 Online monitor and discharge test could view test data, test pattern, cell contrast, maintenance solution.

                          E.jpg

Technical Index

Model

OREN-DC10-480V-110A

wide voltage range battery load bank

String  Voltage Test Range

10V-18V

18V-170V

170V-480V

String Voltage Resolution

0.01V

0.01V

0.01V

Voltage Test Accuracy

0.5%

0.5%

0.5%

Discharge Power Range

600W-15000W

Discharge CurrentRange

0-50A

0-110A

0-55A

Discharge Current Resolution

0.1A

0.1A

0.1A

Current Accuracy

1%

1%

1%

Cell Voltage Type

 

1.2V/2V/6V/12V

Cell Voltage Test Range

1.2V:02V

2V:04V

6V:08V

12V:015V

Cell VoltageResolution

1.2V/2V/6V:0.001V

12V:0.01V

Working Voltage

220Vac(-20%--+30%), 45-65Hz

Breakdown Test

InputCase2200Vdc 1min

InputOutput2200Vdc 1min

OutputCase700Vdc 1min

Safety standard

                              EN610950

Communication

RS232 and SD card communication

Display

7 inch LCD color touch screen

Temperature

Working environment-550

Storage condition-4070

Humidity

090%40±2

Noise

60dB

Altitude

4000M

Cooling

Force air cooling

Weight

Less than 50kg

Related products
Inquiries