中文简体 English

Telephone: ++86 029-68229739

E-mail: sales@oren-electric.com

Current location: Home > Product > Contents

Storage Battery data logging devices

Storage battery data logging devices is dedicated lead-acid battery group monitoring, battery monomer voltage is 2V, 6V or 12V , the equipment adopt advanced testing technical, design according to the relevant state testing and maintenance instruction. The equipment is small and light, have full-featured data management software, can reduce the daily work for battery testing and maintenance.

Send enquiry
Product details

Storage Battery data logging devices

Storage battery data logging devices is dedicated lead-acid battery group monitoring, battery monomer voltage is 2V, 6V or 12V , the equipment adopt advanced testing technical.

The equipment is small and light,  have full-featured data management software, can reduce the daily work for battery testing and maintenance.  

Main Function and Characteristics

 Instrument adopts touch screen operation, can use by touch pen or finger to operate screen

l  Save testing data , has internal storage and SD card

l  With over-voltage, over-current, overheating protection functions.

l  when the battery pack is under the state of online discharge, uniform charge and floating charge, For real-time monitoring of battery pack: including all group of voltage, single-cell voltage, charge/discharge current of all battery pack , charge/discharge capacity of battery pack, Monitoring time of battery, etc;

l  High brightness color LCD screen, display is clear and beautiful.

l  The tester has powerful management software; it can provide data management, printing, analysis, reports statistics, automatic generation of test reports function.

Specification

Model

Data Logging Devices

Cell battery measurement type

2V/6V/12V

cell voltage measurement range

2V:0~4V; 6V:0~8V; 12V:0~15V

cell voltage resolution

2V/6V:0.001V; 12V:0.01V

Battery pack voltage measurement range

0600V

Battery pack voltage measurement resolution

60V: 0.01V; >60V: 0.1V

Voltage testing accuracy

0.5%

Current testing accuracy

1%

Current monitoring range

0300A

working voltage

AC 120V 60Hz

Working environment

040, 20%80%RH

Storage conditions

-2070Packaging store

Communication mode

RS232 communication and USB communications

Display mode

LCD with high brightness and lardge screen.

external dimensions(mm)

230*230*50(mm)

Weight(kg)

1Kg

Carry method

Portable hand-held