400VAC 600KW- R Ac Load Bank
Resistive load bank(AC Load Bank, Dummy Load Bank, Generator Load Bank, Load Bank for Generator Testing) is a device which can simulate the real-life resistive loads and provides a rigorous test regime for power supplies from 1kW to 60MW.
400VAC 600KW- R Ac Load Bank
AC Load Bank Type:
Resistive Load Bank ( PF=1.0);
Inductive Load Bank (PF=0.8)
Voltage : AC 3P4W, 110V-480V 50/60Hz
Main Functions and Features :
1. Can load any power within rated power, test stable state three-phase voltage, current, active power, reactive power, apparent power, power factor, frequency, running time of generating set.
2. Control Mode : Local Panel control or intelligent remote control ( PC software )
3. Control Mode interlock :for both control mode, if choose one of them , another control mode will be locked
4. Data Management processing software , could form curve of current, active power, reactive power, apparentpower, power factor, can be printed.
5. 3 line LED multi-function meter display
6. Protection : Emergency stop Button; over-load protection; over-heat protection; Short Circuit Protection; Fan Protection
Technical Index:
Technical Specifications |
|
Model |
OREN-AC400V-600KW-R Resistive AC Load Bank |
Load Element |
Alloy resistors |
Load Voltage |
AC400V 3phase 4wire, 50Hz |
Load Power |
Resistive: 600KW for AC400V 3phase 4wire, 50Hz |
Load Steps @AC400V 3P4W |
Resistive Load Steps (three phase controlled): 10KW, 20KW*2, 50KW*11 (10-600KW adjustable) |
Power Factor |
PF=1.0 |
Load Accuracy |
±5% |
Digital Meter |
Voltage, Current, Power, Frequency, Power Factor and etc. |
Control Power |
AC400V 3phase 4wire 50/60Hz (Load bank fans & control power supply) |
Control Mode |
1. Manual control by push button 2. Remote control by PC software(optional) |
Wire Connections |
Copper bus bar for wire connections |
Insulation Class |
F |
Fan Noise |
90dB |
Cooling Mode |
Force-air cooling |
Work Mode |
Continuous work |
Protections |
Overheating/buzzer alarm, overheating/over voltage protection, emergency stop button |
Ambient Temperature |
-10℃~+50℃ |
Dimension |
1100*1370*1826mm(W*D*H) |
Weight |
900KG |
Mobility |
6 wheels |
Humidity |
≤95% |
Altitude |
≤2500 meters |